Siemens SENTRON PAC4200 Manual page 19

Power monitoring device
Hide thumbs Also See for SENTRON PAC4200:
Table of Contents

Advertisement

Counters
● A total of 10 energy counters capture reactive energy, apparent energy, and active
energy for off-peak and on-peak, import and export.
● Configurable universal counter for counting
– Limit violations
– Status changes at the digital input
– Status changes at the digital output
– Pulses of a connected pulse encoder, such as electricity, gas, or water meters. The
● Operating hours counter for monitoring the operating time of a connected load. Counts
only in the case of energy counting above an adjustable threshold
Monitoring functions
The following can be monitored:
● 12 limits The limit values can be logically combined. A group message that indicates the
violation of at least one limit value can be generated.
● Direction of rotation.
● Status of the digital inputs.
● Operating status of SENTRON PAC4200.
● Resetting the device and the communication parameters to the factory default settings.
● Deleting recorded load profiles and events
● Resetting counter values
● Reboot after losing the power supply.
● Changing the date and the time.
● Changing device parameters.
● Writing a large number of events in the event memory.
Events and messages
● Recording up to 4096 events with a time stamp and event-specific information.
● Displaying the events in an events list.
● Reporting the events on the display.
● Classifying the messages as information, warnings, or alarms.
Displays and controls
● Large backlit graphics LC display for optimal readability even from a distance.
● Menu-driven parameterization and operation with plaintext display.
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
pulse shape and dynamic response must correspond to the signal shape described in
the IEC 62053-31 standard
Description
3.1 Features
19