Parameterizing
9.2 Parameterizing the operator interface
MODE
SYNC LENGTH
SOURCE
128
ROTATION
SYNC
LIM.VIOLATION
ENERGY PULSE
Default value: OFF.
The field is available when the action "ENERGY PULSE" is selected.
Pulses or edges are output.
PULSE: Pulses are output.
EDGE: Edges are output.
Default value: PULSE
The field is available when the action "SYNC" is selected.
Length of the synchronization pulse. Time for which the signal at the
digital output is "high".
Range: 30 ... 500 ms
Default value: 100 ms
The field is available in the case of the actions "LIM.VIOLATION" and
"ENERGY PULSE"
In the case of the action "LIM.VIOLATION":
the field "SOURCE" selects the limit whose status is given at the digital
output.
The digital output is activated by a
clockwise electrical field and remains active
as long as the field's direction of rotation
remains unchanged.
Synchronization of other devices.
The digital output is switched on by a limit
violation and remains active while the limit
violation prevails.
The field "SOURCE" selects the limit to be
monitored. The definition of the limit is
stored in "ADVANCED > LIMITS".
The digital output outputs the
parameterized number of pulses or edges
per energy unit.
Manual, 09/2008, A5E02316180B-01
SENTRON PAC4200