Historical Load Profile; Table 3- 4 Historical Load Profile - Siemens SENTRON PAC4200 Manual

Power monitoring device
Hide thumbs Also See for SENTRON PAC4200:
Table of Contents

Advertisement

Description
3.4 Load profile
Calculation of the power demand and the cumulated power
Arithmetic power demand:
Arithmetic calculation of the power demand referred to the actual length of the demand
period. The arithmetic power demand in the instantaneous period remains constant providing
the power is constant.
Cumulated power:
Cumulative calculation of the power referred to the configured length of the subperiod. The
cumulated power in the instantaneous period increases linearly providing the power is
constant.
The energy can be calculated from the cumulated power as follows:
See also
Power demand (Page 125)
3.4.2

Historical load profile

Measured variables recorded
SENTRON PAC4200 records the following measured variables:
Table 3- 4
Measured variable
Active power import
Active power export
Reactive power import
Reactive power export
Apparent power
The values are recorded per demand period or subperiod:
● Fixed block method
All values are recorded per demand period.
● Rolling block method
Arithmetic power demand values are recorded per demand period.
Cumulated power demand values and maximum / minimum values are recorded per
subperiod.
32
Energy = (cumulated power) • (configured period length)
Historical load profile
Cumulated
power
X
X
X
X
X
Power
Minimum
demand
instantaneous
value
X
X
X
X
X
Manual, 09/2008, A5E02316180B-01
Maximum
instantaneous
value
±X
±X
±X
±X
X
X
SENTRON PAC4200

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents