Digital Outputs - Siemens SENTRON PAC4200 Manual

Power monitoring device
Hide thumbs Also See for SENTRON PAC4200:
Table of Contents

Advertisement

Technical data
11.1 Technical data
Digital inputs
Number
Input voltage
Input current
Max. input delay

Digital outputs

Number
Design/function
Operating voltage
Output current
Internal resistance
Short-circuit protection
Overvoltage category
Pulse output function
Switching function
Max. switching frequency
156
Rated value
Maximum input voltage
Permissible signal level for signal
"0" detection
Permissible signal level for signal
"1" detection
For signal "1"
Signal "0" to "1"
Signal "1" to "0"
With "1" signal
Continuous load
Transient overload
Resistive load
With "0" signal
Standard for pulse emitter
Adjustable pulse duration
Minimal settable time frame
Max. output delay
With signal "0" to "1"
With signal "1" to "0"
2 inputs
24 V DC
30 V DC (SELV or PELV supply)
< 10 V DC
> 19 V DC
typ. 4 mA (24 V)
5 ms
5 ms
2 outputs
Switching output or pulse output
12 to 24 V DC, max. 30 V DC (SELV or PELV
supply)
Depends on the load and the external power
supply
Max. 100 mA
(thermal overload protection)
max. 300 mA for a duration of 100 ms
100 mA
max. 0.2 mA
55 Ω
Yes
CAT I
Signal characteristics in accordance with
IEC 62053-31
30 to 500 ms
10 ms
5 ms
5 ms
17 Hz
Manual, 09/2008, A5E02316180B-01
SENTRON PAC4200