Modbus Communication Parameter With The Function Codes 0X03, 0X04 And 0X10; Table A- 16 Communication Parameters - Siemens SENTRON PAC3100 Manual

Power monitoring device
Hide thumbs Also See for SENTRON PAC3100:
Table of Contents

Advertisement

A.2.10

MODBUS communication parameter with the function codes 0x03, 0x04 and 0x10

Addressing the communication parameters
Table A- 16
Communication parameters
Offset
Number of
Name
registers
63007
2
Bootloader version
63009
2
Password protection
ON/OFF
63019
2
MODBUS address
63021
2
Baud rate
63023
2
Data bits / Parity bits
/ Stop bits
63025
2
Response time
SENTRON PAC3100
Manual, 07/2009, A5E02385159B-01
Unit
Format
-
unsigned long
-
unsigned long
-
unsigned long
-
unsigned long
-
unsigned long
ms
unsigned long
Applicable
Value range
MODBUS
from ... to
function codes
0x03
char, uchar,
uchar, uchar
0x04
0x03
0, 1
0x04
0x03
1 ... 247
0x04
0x10
0x03
0 = 4,800 baud
1 = 9,600 baud
0x04
2 = 19,200 baud
0x10
3 = 38,400 baud
0x03
0 =
8N2
0x04
1 =
8E1
0x10
2 =
8O1
3 =
8N1
0x03
0 ... 255
0 = Auto
0x04
0x10
Appendix
A.2 Modbus RTU
Access
R
R
RW
RW
RW
RW
137