6.6 Speed/torque command gain and bias

6.6.1 Using two types of frequency (speed) commands





Function
These parameters switch two types of frequency
Switching by parameter setting
Automatic switching by means of switching frequencies
Switching with input terminal
1) One frequency (speed) reference
Reference priority selection =(Default setting)
Priority is given to the reference set with .
2)
Switching with input terminal (
Reference can be switched if the frequency priority switching function is assigned to a terminal.


Ex.) When the frequency priority switching function is assigned to terminal S4.
Title

Speed setting mode selection
Reference priority selection
Speed setting mode selection #2
  switching frequency



has priority
has priority
Function
Input terminal selection #8(S4)
OFF
ON
=)
Frequency priority switching terminal OFF
Frequency priority switching terminal ON
Adjustment range
 
Reference priority
 has priority
 has priority
F-11
Frequency(speed) reference
Frequency reference
Setting value
 (Frequency reference
priority switching)