Fx 2N -16Eys (Triac Output: 16 Points); Product Specifications - Mitsubishi FX3U SERIES User Manual

Hide thumbs Also See for FX3U SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3U
User's Manual - Hardware Edition
16.13 FX
-16EYS (Triac Output: 16 Points)
2N

16.13.1 Product specifications

The generic specifications are identical to the main unit specifications.
For external wiring, refer to the following chapter.
1. Power supply specifications
Item
Product type
Rated voltage
2. Weight and Other specifications
Item
MASS (Weight)
Other
3. Output specifications (Triac output type)
Item
Output points
Connection unit
Output unit
External power supply
Output circuit insulation method
Indication of output operation
Maximum load
Open circuit leakage current
Minimum load
Response time
Output circuit diagram
24V DC (supplied from main unit and input/output powered extension unit)
• The extension cable is already connected to the extension block.
• Accessories: Label for indication of input/output number
• The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Activation of the photo-thyristor will light the LED indicator lamp on panel.
Resistance
The total load current per common should be as follows:
load
• 8 output points/common: 0.8A or less
Inductive load
OFF→ON
ON→OFF
16 FX2N-8/16E*-*(Input/Output Extension Blocks)
16.13 FX2N-16EYS (Triac Output: 16 Points)
→ Refer to Section 4.1 for generic specifications.
→ Refer to Chapter 12 for output wiring.
FX
-16EYS
2N
FX
extension block
2N
FX
-16EYS
2N
0.3 kg (0.66lbs)
FX
-16EYS
2N
16 points
Vertical terminal block (M3 screws)
Triac output (SSR)
85 to 242V AC
Photo-coupler insulation
0.3 A/point
15 VA/100V AC, 30 VA/200V AC
1 mA/100V AC, 2 mA/200V AC
0.4 VA/100V AC, 1.6 VA/200V AC
1 ms or less
10 ms or less
Load
Y
Fuse
U
COM
AC power
supply
A common number applies to the
of [COM ].
323
11
12
13
14
15
16
17
18
19
20