Examples of External Wiring [AC Power Supply Type]

9.5.1

Example of input/output wiring with 24V DC service power supply

24V DC service power supply of the main unit can be used as a power supply for loads.
However, the power consumed by extension devices should be subtracted from the 24V DC service power,
and the remainder can be used as power for loads.
In the case of sink input wiring
Main unit
5V 0V 24V
Input extension block
5V 0V 24V
*1 Connect the AC power supply to the L and N
terminals (in any case of 100V AC system and
200V AC system).
As for the details, see "WIRING PRECAUTIONS"
at "Safety Precautions" field.
*1
L
Class D
grounding
N
S/S
0V
0V
24V
X0
X1
X7
Input
impedance
COM1
Y0
Y1
Y3
Load
*2
S/S
X0
X1
9 Preparation for Wiring and Power Supply Wiring Procedures
9.5 Examples of External Wiring [AC Power Supply Type]
AC power supply of
PL
MC
MC
Power supply for loads
24V
connected to sequencer
output terminals
As for the details of
emergency stop, see
"DESIGN PRECAUTIONS"
at "Safety Precautions"
field.
In the case of source input wiring
S/S
0V
24V
Fuse
*2 Connect the 24V terminal (in the case of sink input)
or the 0V terminal (in the case of source input) to
the S/S terminal on the input extension block.
100 to 240V
Breaker
Power ON
MC
Emergency
stop
MC
0V
24V