Mitsubishi FX3U SERIES User Manual page 262

Hide thumbs Also See for FX3U SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3U
User's Manual - Hardware Edition
Error
PLC operation at
code
error occurrence
PLC/PP communication error (D8062)
0000
6201
6202
Continues
6203
operation
6204
6205
Serial communication error 1 [M8063 (D8063)]
0000
6301
6302
6303
6304
6305
6306
Continues
operation
6307
6308
6312
6313
6314
6320
Parameter error [M8064(D8064)]
0000
6401
6402
6403
6404
Stops
6405
operation
6406
6407
6409
Syntax error [M8065(D8065)]
0000
6501
6502
6503
Stops
6504
operation
6505
6506
6507
6508
6509
6510
256
Contents of error
No error
Parity, overrun or framing error
Communication character error
Communication data sum check error
Data format error
Command error
No error
Parity, overrun or framing error
Communication character error
Communication data sum check error
Communication data format error
Command error
Communication time-out detected
Modem initialization error
N:N network parameter error
Parallel link character error
Parallel link sum error
Parallel link format error
Inverter communication error
No error
Program sum check error
Memory capacity setting error
Latched device area setting error
Comment area setting error
File register area setting error
Special unit (BFM) initial value setting, positioning
instruction setting sum check error
Special unit (BFM) initial value setting, positioning
instruction setting error
Other setting error
No error
Incorrect combination of instruction, device symbol
and device number
No OUT T or OUT C before setting value
• No setting value after OUT T or OUT C
• Insufficient number of operands for an applied
instruction
• Same label number is used more than once.
• Same interrupt input or high speed counter
input is used more than once.
Device number is out of allowed range.
Invalid instruction
Invalid label number [P]
Invalid interrupt input [I]
Other error
MC nesting number error
14 Test Operation, Adjustment, Maintenance and Troubleshooting
14.6 Judgment by Error Codes and Representation of Error Codes
Error codes in shaded columns are added in FX
Check the cable connection between the
programming panel (PP) / programming device and
the PLC. This error may occur when a cable is
disconnected and reconnected during PLC
monitoring.
• Inverter communication, computer link and
programming:
Ensure that the communication parameters are
correctly set according to their applications.
• N:N network, parallel link, etc.:
Check programs according to applications.
• Remote maintenance:
Ensure modem power is ON and check the
settings of the AT commands.
• Wiring:
Check the communication cables for correct
wiring.
STOP the PLC, and correctly set the parameters.
During programming, each instruction is checked. If
a syntax error is detected, modify the instruction
correctly.
PLCs.
3U
Action

Advertisement

Table of Contents
loading

Table of Contents