WIRING PRECAUTIONS
• Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or
extension units.
Doing so may cause damage to the product.
• Perform class D grounding (grounding resistance: 100 Ω or less) to the grounding terminal on the main unit and
extension units with a wire 2 mm
Do not use common grounding with heavy electrical systems (refer to Section 9.4).
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to properly wire the FX
the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N
264
2
or thicker.
/FX
/FX
Series extension equipment to the main unit in accordance with
0N
2N
3U
m.