External Dimensions; Terminal Layout - Mitsubishi FX3U SERIES User Manual

Hide thumbs Also See for FX3U SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3U
User's Manual - Hardware Edition
3. Output specifications (triac output type)
Item
Number of output points
Connection type
Output unit
External power supply
Output circuit insulation
Indication of output operation
Max. load
Open circuit leakage current
Min. load
Response time
Output circuit diagram

15.7.2 External dimensions

FX
-32ES
2N
2-φ4.5 mounting holes
L
N
Y0
Y2
COM1
Y1
140 (5.52") (mounting hole pitch)
150 (5.91")

15.7.3 Terminal layout

FX
-32ES
2N
COM
L
N
Y0
Y2
Y1
Y3
COM1
282
Resistance
The total load current per common terminal should be the following value.
load
• 4 output points/common terminal: 0.8 A or less
Inductive load
OFF→ON
ON→OFF
COM
X0
X2
X4
X6
X0
X2
X4
X6
24+
X1
X3
X5
X7
X1
X3
X5
X7
0
1
2
3
4 5 6
7
IN
0
1
2
3
4 5 6
7
POWER
0
1
2
3
4 5 6
7
FX
-32ES
OUT
2N
0
1
2
3
4 5 6
7
TRIAC UNIT
Y4
Y6
Y0
Y2
Y4
Y6
Y3
COM2
Y5
Y7
COM3
Y1
Y3
COM4
Y5
Y7
X0
X2
X4
X6
X0
X2
24+
X1
X3
X5
X7
X1
Y4
Y6
Y0
Y2
Y5
Y7
Y1
Y3
COM2
COM3
COM4
15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
Removable terminal block (M3 screw)
Triac output (SSR)
85 to 242V AC
Insulation with photo-thyristor
When photo-thyristor is driven, LED on panel is lit.
15 VA/100V AC, 30 VA/200V AC
1 mA/100V AC, 2 mA/200V AC
0.4 VA/100V AC, 1.6 VA/200V AC
10 ms or less
Load
External
power supply
Fuse
A common number applies to the
Unit : mm (inches)
87 (3.43")
X4
X6
X3
X5
X7
Y4
Y6
Y5
Y7
FX
-32ES
2N
16 points
0.3A/point
1 ms or less
Y
U
COM
of [COM
9 (0.36")
The terminal block uses
M3 terminal screws.
15.7 FX2N-32ES
].