Transistor Output (Source Type) - Mitsubishi FX3U SERIES User Manual

Hide thumbs Also See for FX3U SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3U
User's Manual - Hardware Edition
4.4.4

Transistor output (source type)

The output numbers in the table indicate the main unit terminal numbers. "Y010 or more" means the numbers
from Y010 to the largest number that the main unit has.
(The output numbers of FX
Item
Number of output
points
Connecting type
Output type/form
External power supply
Resistance
load
Max. load
Inductive
load
Open circuit leakage
current
ON voltage
Min. load
OFF→ON
Response
time
ON→OFF
Circuit insulation
Display of output
operation
Output circuit
configuration
56
4 Specifications, External Dimensions and Terminal Layout (Main Units)
-16MT/ SS are Y000 to Y007.)
3U
Transistor output (source) specifications
FX
-16MT/
FX
-32MT/
3U
3U
SS
SS
8 points
16 points
Fixed terminal
block
(M3 screw)
The total load current of resistance loads per common terminal should be the following value.
• 1 output point/common terminal: 0.5 A or less
• 4 output points/common terminal: 0.8 A or less
• 8 output points/common terminal: 1.6 A or less
Y000 to Y002:5 µs or less/10 mA or more (5 to 24V DC)
Y003 or more:0.2 ms or less/200 mA or more (at 24V DC)
Y000 to Y002:5 µs or less/10 mA or more (5 to 24V DC)
Y003 or more:0.2 ms or less/200 mA or more (at 24V DC)
Photocoupler insulation
LED on panel lights when photocoupler is driven.
Fuse
A common number applies to the
FX
-48MT/
FX
-64MT/
3U
3U
SS
SS
24 points
32 points
Removable terminal block (M3 screw)
Transistor/source output
5 to 30V DC
0.5A / point
→ For details on the common terminal for each model,
12W/24V DC
0.1 mA or less/30V DC
1.5 V or less
Load
Y
+V
DC power
supply
4.4 Output Specifications
FX
-80MT/
FX
-128MT/
3U
3U
SS
ESS
40 points
64 points
refer to the terminal block layout.
of [+V
].

Advertisement