Output Specifications (Main Unit) Transistor Output (Source Type) - Mitsubishi FX3U SERIES User Manual

Hide thumbs Also See for FX3U SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3U
User's Manual - Hardware Edition

12.3.2 Output specifications (main unit) transistor output (source type)

Item
Number of output
points
Connecting type
Output type/form
External power
supply
Resistance
load
Max. load
Inductive
load
Open circuit leakage
current
ON voltage
Min. load
OFF→ON
Response
time
ON→OFF
Circuit insulation
Display of output
operation
Output circuit
configuration
Number of output points per common terminal
• On FX
-16M/ SS, one common terminal is used for 1 output point.
3U
• On models other than FX
Transistor output (source) specifications
FX
-16MT/
FX
-32MT/
3U
3U
SS
SS
8 points
16 points
Fixed terminal
block
(M3 screw)
The total load current of resistance loads per common terminal should be the following
value.
• 1 output point/common terminal: 0.5 A or less
• 4 output points/common terminal: 0.8 A or less
• 8 output points/common terminal: 1.6 A or less
Y000 to Y002:5 µs or less/10 mA or more (5 to 24V DC)
Y003 or more:0.2 ms or less/200 mA or more (at 24V DC)
Y000 to Y002:5 µs or less/10 mA or more (5 to 24V DC)
Y003 or more:0.2 ms or less/200 mA or more (at 24V DC)
Photocoupler insulation
LED on panel lights when photocoupler is driven.
Load
Fuse
DC power
A common number applies to the
-16MT/ SS, 1 common terminal is used for 4 or 8 output points.
3U
12.3 External Wiring of Transistor Output (Sink/Source) Type
FX
-48MT/
FX
-64MT/
3U
3U
SS
SS
24 points
32 points
Removable terminal block (M3 screw)
Transistor/source output
5 to 30V DC
0.5A / point
→ For details on the common terminal for each model,
refer to the terminal block layout.
12W/24V DC
0.1 mA or less/30V DC
1.5 V or less
Y
+V
supply
of [+V
12 Output Wiring Procedures
FX
-80MT/
FX
-128MT/
3U
3U
SS
ESS
40 points
64 points
].
213
11
12
13
14
15
16
17
18
19
20

Advertisement

Table of Contents
loading

Table of Contents