9.3.2

DC Power Supply Type

Item
Supply voltage
Allowable supply voltage
range
Allowable instantaneous
power failure time
Power fuse
Power consumption
Rush current
24V DC service power
supply
5V DC built-in power
*2
supply
*1.
This power consumption is the value maximized by input/output extension blocks and special function
units/blocks connected to the main unit.
*2.
The power supply is not for external use.
The current capacity specified above is for the input/output extension blocks, special function blocks,
special adapters and expansion boards.
*3.
When supply voltage is 16.8 to 19.2V DC, the connectable extension equipment decreases.
For details, refer to Subsection 6.5.3 or 6.5.4.
FX
-16M /D
FX
3U
3U
Operation can be continued upon occurrence of instantaneous power failure for 5 ms or less.
250V, 3.15A
*1
25W
→ For input/output powered extension units/blocks power consumption information,
9 Preparation for Wiring and Power Supply Wiring Procedures
Specifications
-32M /D
FX
-48M /D
3U
24V DC
16.8 to 28.8V DC
30W
35W
35 A max. 0.5 ms or less/24V DC
500 mA or less
9.3 Power Supply Specifications
FX
-64M /D
FX
-80M /D
3U
3U
*3
250V, 5A
40W
45W
refer to Section 15.2.