5. Response time
The time from when the PLC drives (or shuts down) the photocoupler until the transistor is turned on (or off) is
shown in the following table.
Classification
Y000 to Y002
Main unit
Y003 or more
Input/output powered extension unit
Output extension block
*1.
The transistor OFF time is longer under lighter loads.
For example, under a load of 24V DC 40mA, the response time is approx. 0.3ms. When response
performance is required under light loads, provide a dummy resistance as shown to the right to
increase the load current.
- Sink output type
Fuse
Load
6. Output current
The maximum resistance loads for the input/output powered extension units and output extension blocks are
shown in the following table.
The ON voltage of the output transistor is approx. 1.5V.
When driving a semiconductor element, carefully check the input voltage characteristics of the applied
element.
Main unit
Input/output powered
extension units
Extension block
7. Open circuit leakage current
0.1mA or less
Response time
5 µs or less
0.2 ms or less
0.2ms or less
PLC
Dummy
resistance
Y
COM1
Model
Output current
FX
-16MT-ES(S)
3U
FX
-32MT-ES(S)
3U
FX
-48MT-ES(S)
3U
FX
-64MT-ES(S)
3U
FX
-80MT-ES(S)
3U
FX
-128MT-ES(S)
3U
FX
-32ET-ESS/UL
2N
FX
-48ET-ESS/UL
2N
FX
-48ET-DSS
2N
FX
-32ET
2N
FX
-48ET
2N
FX
-48ET-D
2N
FX
-16EYT-ESS/UL
2N
FX
-8EYT-ESS/UL
2N
FX
-16EYT
2N
FX
-8EYT
2N
FX
-8EYT-H
2N
FX
-16EYT-C
2N
12.3 External Wiring of Transistor Output (Sink/Source) Type
Load current
5 to 24V
When using an instruction related to pulse train
DC 10mA
output or positioning, make sure to set the load
or more
current to 10 to 100 mA (5 to 24V DC).
24V DC 200 mA or more
*1
24V DC 200 mA
- Source output type
Dummy
Fuse
Load
resistance
The total load current of resistance loads per
common terminal should be the following value.
1 point/common: 0.5A or less
4 points/common: 0.8A or less
0.5A/point
8 points/common: 1.6A or less
For FX
-16EYT-C:
2N
16 points/common: 1.6A or less
For FX
-8EYT-H:
2N
4 points/common: 2A or less
1A/point
0.3A/point
12 Output Wiring Procedures
*1
PLC
Y
+V0
Limitation
11
12
13
14
15
16
17
18
19
20