OMNI-408/OMNI-408EU Installation and Setup Guide
#58 COMMAND: When selected, enables user's access to the #58 quick command to enter or change
the Pager Follow-Me phone number. If this feature is not enabled, the user will not be able to enter or
change a pager phone number.
PAGER OPEN/CLOSE USER SELECT: Selects whether user codes 1-6 or 4-6 only are authorized for
pager openings and closings. If the bit for pager openings and closings is set and this user bit is not set,
then all users are enabled for opening and closing pager. With this user bit set, the open/close pager
capabilities are limited to users 4-6 only. The Pager Toggle ([#] [8]) quick command feature gives any
user the ability to toggle on/off the ability for open/close events, if the events are enabled, by tripping
the pager.
NOTE: Keyfob users are considered 9-14 and are not affected by this option.
PAGER ATTEMPTS: Selects the number of attempts for dialing the Pager Follow-Me phone number.
If the bit is set, 2 attempts are made. If the bit is not set, then 1 attempt is made.
EXIT BYPASS: The Exit Bypass feature disables the Exit Error feature. When selected, any delay
zone or interior that is violated at the end of exit time is bypassed for that armed period.
QUESTION 27
NONSUPERVISED/TAMPER RF ZONES
There are 4 locations (L1-L4) in this question:
U L
RF has not been evaluated by UL and must not be used for UL installations.
Question 27, L1 & L2 - Nonsupervised RF Zones
Select the RF zones not to be supervised. This refers to wireless transmitters that will be removed from
the premises and will be out of the receiver's range. To avoid generating CS transmissions (RF point
supervisory), they MUST NOT be supervised. Select the nonsupervised RF zones from the tables below.
NOTE: The checkmarks indicate which points are selected. Keyfobs are not included.
L1 - Nonsupervised Zones 5-8
NONSUPERVISED ZONES
Digit
5
0
None (All RF Zones Supervised)
1
2
3
4
5
6
7
8
9
A
B
C
D
7–26
6
7
8
L2 - Nonsupervised Zones 1-4
NONSUPERVISED ZONES
Digit
1
2
0
None (All RF Zones Supervised)
1
2
3
4
5
6
7
8
9
A
B
C
D
DEFAULT = 0000
Default = 00
3
4