OMNI-408/OMNI-408EU Installation and Setup Guide
CS TEST TIME INTERVAL - There are 2 modes of test transmission for the CS Test Time Interval.
One mode is reset by an event and the other mode operates only by time, as described below. Enter the
CS code in Question 21, Locations 3 and 4.
CS TEST BY EVENT - If this feature is enabled, the system transmits the Test code to the central
station at the interval selected, in the absence of any other signal. Select from daily (24-hour), weekly,
27 days, 60 days, or 90 days. Transmission of any signal resets the CS Test clock. For example, if a
business opens and closes 6 days a week, then a test signal is generated at the interval selected after
the last closing signal.
CS TEST BY TIME - If this feature is enabled, the system transmits the Test code to the central
station at the interval selected. Select from daily (24-hour), weekly, 27 days, 60 days, or 90 days. For
example, if a 24-hour CS Test is selected, the CS Test signal is sent to the central station every 24
hours.
U L
Must be programmed as "3" for UL installations.
Question 09, L4
RF Trouble Sounder, AC Loss Sounder & Euro. Ring Detect
RF PROGRAM USING
Digit
BYPASS KEY
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
RF PROGRAMMING ACCESS USING THE BYPASS KEY - Allows the installer to select the
procedure for accessing the RF program questions in Installer programming mode. If the bit is NOT
enabled, the procedure for RF programming requires pressing the [*] key followed by the [#] key
7–12
RF TROUBLE
AC LOSS
SOUNDER
SOUNDER
NONE
Default = 6
EUROPEAN RING