C7: Voltage Adjustment - YASKAWA U1000 Technical Manual

Matrix drive low harmonic regenerative drive for industrial applications 200 v class: 7.5 to 75 kw (10 to 100 hp nd) 400 v class: 5.5 to 580 kw (7.5 to 775 hp nd)
Hide thumbs Also See for U1000:
Table of Contents

Advertisement

Setting a Variable Carrier Frequency (V/f Control)
In V/f Control, the carrier frequency can be set up to change linearly with the output frequency by setting the upper and lower
limits for the carrier frequency and the carrier frequency proportional gain (C6-03, C6-04, C6-05).
n
C6-09: Carrier Frequency during Rotational Auto-Tuning
Determines the carrier frequency while performing Rotational Auto-Tuning. Although this parameter rarely needs to be
changed, when overcurrent problems occur when Auto-Tuning a high frequency motor or low impedance motor, it may be
helpful to set C6-03 to a high value before setting C6-09 to 1.
No.
C6-09
Carrier Frequency during Rotational Auto-Tuning
Setting 0: Carrier frequency = 4 kHz
Setting 1: Same value set to C6-03
u

C7: Voltage Adjustment

n
C7-43: Input Voltage Offset Adjustment
Note:
Adjustment is completed at the factory. Do not change the setting of this parameter.
Enables adjustment of the offset for the input voltage circuit when the control board is replaced.
Changing the value of o2-04 will trigger an oPE30 error. The input voltage offset must be adjusted when the error occurs. If
the combination of the control board and drive does not change, set this parameter to 0002 (offset adjustment not required).
Contact Yaskawa or a Yaskawa representative if it becomes necessary to replace the control board.
No.
C7-43
Setting 0000: Standard
Setting 0002: Offset Adjustment Not Required
n
C7-56: Power Factor Control Selection
Power factor control improves the input power supply power factor according to the operating conditions.
This parameter rarely requires adjustment, but may be enabled to improve the power factor in the low output region. Power
factor control is not suitable for applications with frequent load fluctuations.
This function is disabled in High Output Voltage Mode (C7-60 = 1).
No.
C7-56
Setting 0: Power Factor Control Disabled
Setting 1: Power Factor Control Enabled
n
C7-60: Output Voltage Limit Mode Selection
Sets the mode to limit the output voltage.
Set this parameter to 0 (Harmonic suppression priority mode) to give priority to harmonic suppression. The maximum output
voltage is automatically limited to suppress harmonics.
Set this parameter to 1 (High output voltage mode) to give priority to the output voltage over harmonic suppression. The
effectiveness of harmonic suppression will be reduced because the maximum output voltage will be used.
No.
C7-60
Setting 0: Harmonic Suppression Priority Mode
Setting 1: High Output Voltage Mode
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Parameter Name
Parameter Name
Input Voltage Offset Adjustment
Parameter Name
Power Factor Control Selection
Parameter Name
Output Voltage Limit Mode Selection
Setting Range
0, 1
Setting Range
0000 to 9999
Setting Range
0, 1
Setting Range
0, 1
5.3 C: Tuning
Default
0
Default
0000
Default
0
5
Default
1
235