E4-11: Motor 2 Rated Power
Sets the motor 2 rated power. If Auto-Tuning completes successfully, the value entered to T1-02 will automatically be saved
to E4-11.
No.
E4-11
u

E5: PM Motor Settings

These parameters set the motor data of a PM motor.
When using Yaskawa motors, set up the E5-oo parameters by entering the motor code written on the motor nameplate.
Perform Auto-Tuning for all other PM motors. The motor data can also be entered manually, if known.
Note:
1. E5-oo parameters are visible only when a PM motor control mode is selected (A1-02 = 5, 6, or 7).
2. E5-oo parameters are not reset when the drive is initialized using parameter A1-03.
When using a Yaskawa motor without a motor code or when using a PM motor from another company, set the parameters
according to the motor nameplate values and test report values.
n
E5-01: Motor Code Selection (for PM Motors)
When using a Yaskawa motor with a motor code, set the motor code for the PM motor being used. The drive automatically
sets several parameters to appropriate values depending on the motor code.
When using a Yaskawa motor without a motor code or a non-Yaskawa PM motor, set the parameters according to the motor
nameplate and test report values.
Setting parameter E5-01 to FFFF allows the motor data to be manually set using the E5-oo parameters.
No.
E5-01
Note:
1. E5-oo parameters are not reset when the drive is initialized using parameter A1-03.
2. When E5-01 is set to a value other than FFFF, the drive will not initialize using parameter A1-03
3. Changing E5-01 to FFFF from value other than FFFF will not change the values of parameters E5-02 through E5-24.
4. Set E5-01 to FFFF when using a motor other than a Yaskawa SMRA, SSR1, or SST4 series.
5. Default settings are:
OLV/PM, AOLV/PM: Yaskawa SSR1 Series (1750 r/min)
CLV/PM: Yaskawa SST4 Series (1750 r/min)
6. Selection may vary depending on the motor code entered to E5-01.
7. If an alarm or hunting occurs despite using a motor code, enter the value indicated on the nameplate.
Magnet Motors on page 158
Figure 5.55
explains the motor code setting.
n
E5-02: Motor Rated Power (for PM Motors)
Sets the rated power of the motor. Determined by the value set to T2-04 during Stationary Auto-Tuning for PM motors or by
entering the motor code to E5-01.
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Parameter Name
Motor 2 Rated Power
Parameter Name
Motor Code Selection (for PM Motors)
for details.
0: Pico Motor
(SMRA Series)
1: Derated Torque for IPM
Motors
(SSR 1 Series)
2: Rated Torque for IPM
Motors
(SST4 Series)
Figure 5.55 PM Motor Code
5.5 E: Motor Parameters
Setting Range
0.00 to 650.00 kW
Setting Range
0000 to FFFF
Refer to Auto-Tuning for Permanent
Motor Voltage Class
and Capacity
0: 1800 r/min Series
1: 3600 r/min Series
2: 1750 r/min Series
3: 1450 r/min Series
4: 1150 r/min Series
F: Special Motor
Default
Determined by
o2-04
Default
Determined by
A1-02, C6-01 and
o2-04
5
261