D7: Offset Frequency - YASKAWA U1000 Technical Manual

Matrix drive low harmonic regenerative drive for industrial applications 200 v class: 7.5 to 75 kw (10 to 100 hp nd) 400 v class: 5.5 to 580 kw (7.5 to 775 hp nd)
Hide thumbs Also See for U1000:
Table of Contents

Advertisement

5.4 d: Reference Settings
No.
d6-06
u

d7: Offset Frequency

n
d7-01 to d7-03: Offset Frequency 1 to 3
Three different offset values can be added to the frequency reference. They can be selected using digital inputs programmed
for Offset frequency 1, 2, and 3 (H1-oo = 44, 45, 46). The selected offset values are added together if multiple inputs are
closed simultaneously. The value is set as a percentage of the Maximum Output Frequency.
Note:
This function can replace the "Trim Control" function (H1-oo = 1C, 1D) of older Yaskawa drives.
No.
d7-01
d7-02
d7-03
Figure 5.52
illustrates the Offset frequency function.
250
Parameter Name
Field Forcing Limit
Parameter Name
Offset Frequency 1
Offset Frequency 2
Offset Frequency 3
Frequency
reference
Offset Frequency 1 [d7-01]
(Signed)
Offset Frequency 2 [d7-02]
(Signed)
Offset Frequency 3 [d7-03]
(Signed)
Figure 5.52 Offset Frequency Operation
Multi-function
input (44) = on
Multi-function
input (45) = on
Multi-function
input (46) = on
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Setting Range
100 to 400%
Setting Range
-100.0 to 100.0%
-100.0 to 100.0%
-100.0 to 100.0%
Frequency
SFS
reference after
soft starter
Default
400%
Default
0%
0%
0%