Pepperl+Fuchs HD2-GTR-4PA Manual page 78

Profibus power hub segment coupler
Hide thumbs Also See for HD2-GTR-4PA:
Table of Contents

Advertisement

Troubleshooting
Symptom
Device diagno-
sis: „Firmware
updated"
PA slaves do not
take part in cy-
clic data ex-
change
PA-Bus-Master
parameters
(WD mode, WD
time, No. of re-
tries, Segment
No.) cannot be
written
Slave not visible
in DCS
ADM error or
module missing
ADM: system
maint. required
ADM: system
out of spec.
ADM: segment
maint. required
ADM: segment
out of spec.
Subject to reasonable modifications due to technical advances.
78
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
P R O F I B U S P
O W E R
Possible cause
Device has not been re-
booted
Redundant system, but
Built-In-Slave has not
been added to cyclic data
exchange
PA-Bus-Master parame-
ters are write-protected
because Built-In-Slave
has been added to cyclic
data exchange using PA
bus configuration module
Respective segment is
deactivated
Poor signal quality on PA
side
Diagnostic Module is de-
fekt or has been removed
(by active ADM Alarm Ob-
server only).
At least one monitored sy-
stem value has violated
the preset limit
At least one monitored sy-
stem value has violated
the specification limit
At least one monitored
segment value has viola-
ted the preset limit
At least one monitored
segment value has viola-
ted the specification limit
H
S
U B
E G M E N T
Remedy
Reboot device. Firmware
is not active until device
has been rebooted
Add Built-In-Slave to cy-
clic data exchange
Use different module to
configure cyclic data ex-
change
Harmonize number of PA
segments at Gateway
and actual number of exi-
sting segments
Perform Physical Layer
Diagnosis on PA side with
Advanced DIagnostic Mo-
dule
Replace Diagnostic
Module
Switch off ADM Alarm
Observer
Execute diagnosis with
DTM Diagnostic Manager
for detail information (for
further information see
Advanced Diagnostic Mo-
dule HD2-DM-A manual).
Copyright Pepperl+Fuchs, Printed in Germany