Technical Data - Pepperl+Fuchs HD2-GTR-4PA Manual

Profibus power hub segment coupler
Hide thumbs Also See for HD2-GTR-4PA:
Table of Contents

Advertisement

P R O F I B U S P
O W E R
2.7

Technical Data

System overview
Ambient conditions:
Ambient temperature
Storage temperature
Relative humidity
Shock resistance
Vibration resistance
Mechanical data:
Protection degree
Motherboard mounting
Conformity to standards:
Shock resistance
Vibration resistance
Fieldbus standard
EMV
Installation in hazardous areas:
Approvals:
HD2-GTR-4PA
Supply:
Rated voltage
Rated current
Power dissipation
Fieldbus interface/PROFIBUS DP:
Connection
Protocol
Galvanic isolation:
PROFIBUS DP/CH
PROFIBUS DP/supply
All circuits/FE
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
H
S
U B
E G M E N T
19.2 to 35 V DC
160... 90 mA
3 W
SUB-D-socket, 9-pin
PROFIBUS DP V1
Functional isolation per IEC 62103,
rated isolation voltage 50 V
C
O U P L E R
-40..60 °C
-40..85 °C
<95% non-condensing
15 g 11 ms
1 g, 58 to 150 Hz
IP 20 acc. to EN 60529
Mounting rail, 35 mm
DIN EN 60068-2-27
DIN EN 60068-2-6
IEC 61158
Namur NE 21
EN 61326
Zone 2
II 3 G Ex nA II T4
Class 1
Division 2
Gas groups IIC, IIB, IIA
Copyright Pepperl+Fuchs, Printed in Germany
Specification
eff
19