When the HD2-GTR-4PA is delivered, the Watchdog setting is set by
default to transparent. You can find further information in chapter "Addi-
tional Information about Watchdog time" on page 33.
Set Fixed Watchdog Time via DTM
To change the Watchdog setting:
1. Open the Online or Offline dialog
2. Select "Fixed" from the drop-down list
•
3. Confirm the entry with Return
4. Enter the Watchdog time and confirm with Return
•
6.3.5
PA Retry Limit Setting
Parameters can also be set for the PA side retry limit in acyclic data ex-
change.
Set the PA Retry Limit via DTM
To set the PA retry limit in the DTM :
1. Open the Online or Offline Dialog
•
2. Select the retry limit from the drop-down list
3. Confirm your entry with Return
6.3.6
Restart Functions, Redundancy Switchover and Firmware Update
The HD2-GTR-4PA-DTM offers three additional functions:
•
Restart,
•
Restart with Default Values and
•
Firmware Update.