Profibus Advanced Diagnostics Integration; Activating Alarm Observer In The Dtm - Pepperl+Fuchs HD2-GTR-4PA Manual

Profibus power hub segment coupler
Hide thumbs Also See for HD2-GTR-4PA:
Table of Contents

Advertisement

P R O F I B U S P
O W E R
Advanced Diagnostics with the PROFIBUS Power Hub
7.2

PROFIBUS Advanced Diagnostics Integration

If the Advanced Diagnostic Module HD2-DM-A is connected via
PROFIBUS DP, the PROFIBUS-Gateway HD2-GTR-4PA acts as the in-
terface and the data access coordinator for diagnostic messages to the
DCS and the DTM if the function "Alarm Observer" has been activated.
If the Alarm Observer is activated, basic warnings and alarms of the
Diagnostic Module are integrated into the slave diagnosis and can be
parsed by the DCS via cyclic data exchange. Additionally, these
warnings and alarms also appear directly in the DTM diagnostic dialog
(Online Parameterization) of the PROFIBUS Gateways.
The Alarm Observer can be switched on both acyclically via the DTM
and cyclically via DCS Gateway configuration.

Activating Alarm Observer in the DTM

1. Open the window Offline or Online Parameterization
2. Choose Alarm Observer Enabled from the DropDown list and con-
firm with Return
Subject to reasonable modifications due to technical advances.