P R O F I B U S P
O W E R
Advanced Diagnostic Module Engineering
Data loss
•
The Advanced Diagnostic Module can be engineered in both the offline
and the online dialog. Make sure to load the data from the device or to
the device after engineering.
Attention
To integrate an Advanced Diagnostic Module HD2-DM-A via
PROFIBUS PA, proceed as follows:
1. In the device catalog, open
PEPPERL+FUCHS GmbH/Device/HD2-DM-A
2. Drag&Drop HD2-DM-A into the project window's HD2-GTR-4PA
node
The ADM address is being detected automatically and is displayed sym-
bolically by „999". There is no need to assign an address.
Note
Your project tree should now look as follows:
•
3. To assign a tag to the Advanced Diagnostic Module, open the off-
line dialog of HD2-GTR-4PA.
4. Enter a device description into the field ADM Tag and confirm with
Enter
•
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
H
S
U B
E G M E N T
C
O U P L E R
PROFIBUS Commissioning
Copyright Pepperl+Fuchs, Printed in Germany
39