Case 3: Simplex

In the simplex system, both the coupling of DP to PA and the supply of
the four segments are single (simplex). The simplex system consists of
the following components:
Gateway motherboard MB-FB-GT
Power Hub motherboard MB-FB-4.GEN
1 x HD2-GTR-4PA
4 x Power Modules
1 x Diagnostic Module
1 x Sub-D cable to connect motherboards
Combining a simplex Gateway Motherboard and a redundant Power Hub
Motherboard also makes a fourth combination possible. Pepperl+Fuchs
does not recommend using this arrangement. Since a fault in the cou-
pling of DP to PA results in failure of all four segments together, but the
Note
failure of a single segment does not have any effect on the remaining
segments, increased segment availability can be achieved most easily
with redundant coupling (as described in case 1 and case 2).