P R O F I B U S P
O W E R
10

Parameter Reference List

10.1

General Parameters

Name
TAG (device)
Reserved
Mounting location
Software version
Serial number
Static revision
Information
Totals status
Number of activated PA seg-
ments
10.1.1

PA Master Parameters

Name
PA Retry Limit
Watchdog mode
Work on the bus (for example connecting or disconnecting field devices)
can cause malfunctions on the bus, which may cause other field devices
to fail. To counteract this problem, the retry limit can be increased. Incre-
asing the retry limit increases the cycle time under some circumstances.
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
H
S
U B
E G M E N T
Description
Device TAG; Default EMPTY
-
Mounting location of the device; Default EMPTY
Software version of the device
Serial number of the device
"Static revision" counter is incremented when non-
volatile values are changed.
Device information in a bit field
Bit 0 = Board Type
• 0 = Non-redundant Motherboard
• 1 = Redundant Motherboard
Bit 1 = Device position on Motherboard*
• 0 = Left device
• 1 = Right device
*0 for non-redundant Motherboard
Combined device status message (good: 0x00;
bad. 0x80)
Number of active PA segments (1...4)
Description
Retry limit of PA Master (valid values: 1...7)
Default: 1 (firmware 2.6.0 or older)
Default: 3 (firmware 2.6.1 or newer)
Value of / working with Watchdog time (WDt):
• 0 = Transparent WDt
• 1= Fixed WDt*
*Valid values 2...25 sec.; Default: 50* 100 ms
C
O U P L E R
Parameter Reference List
Copyright Pepperl+Fuchs, Printed in Germany
69