Modules For Coupling, Supply And Diagnosis - Pepperl+Fuchs HD2-GTR-4PA Manual

Profibus power hub segment coupler
Hide thumbs Also See for HD2-GTR-4PA:
Table of Contents

Advertisement

Specification
Gateway motherboard redundant MB-FB-GTR
The gateway motherboard redundant MB-FB-GTR allows the connec-
tion of the Fieldbus Power Hub motherboards MB-FB*.GEN or MBHD-
FB*.GEN with a standard cable. Two sockets will hold two DP/PA Gate-
ways HD2-GTR-4PA. The Built-In Slaves of the HD2-GTR-4PA modules
can be addressed using the DIP switch on the motherboard.
Power Hub motherboard simplex MB-FB-4.GEN
The MB-FB-4.GEN allows the supply of four Fieldbus segments as well
as the direct connection of the PROFIBUS DP/PA Gateway Mother-
boards MB-FB-GT or MB-FB-GTR with a standard cable. Four sockets
hold the Power Modules. The modules are available for different explo-
sion protection concepts and with various isolation levels. A further sok-
ket holds a Diagnostic Module
Power Hub motherboards redundant MB*-4R.GEN
The MB*-4R.GEN motherboards allow the redundant supply of four
fieldbus segments as well as the direct connection of the PROFIBUS
DP/PA Gateway Motherboards MB-FB-GT or MB-FB-GTR with a stan-
dard cable. Eight sockets hold the power supply modules, two power
supply modules supplying each of the four segments redundantly. The
modules are available for different explosion protection concepts and
with various isolation levels. A further socket holds a Diagnostic Module.
DART Power Hub motherboard redundant MBHD-FB-D-4R.GEN
The MBHD-FB-D-4R.GEN motherboard allows for the redundant supp-
ly of four intrinsically safe Ex ib fieldbus segments as well as the direct
connection of the PROFIBUS DP/PA Gateway Motherboards MB-FB-
GT or MB-FB-GTR with a standard cable. Eight sockets hold the power
supply modules, two power supply modules supplying each of the four
segments redundantly. A further socket holds a Diagnostic Module.
2.4.2

Modules for Coupling, Supply and Diagnosis

Gateway module HD2-GTR-4.PA
The Gateway module provides the connection of four PROFIBUS PA
segments to a PROFIBUS DP. In conjunction with Fieldbus Power Mo-
dules, PA segments are supplied directly via Fieldbus lines. Coupling is
transparent, so each PA device is addressed and configured as a PRO-
FIBUS DP device.
The HD2-GTR-4PA module includes four full-featured PA masters, who
perform data exchange time independently.
The FDT/DTM based PC software package allows the parameterization
of the Gateway and offers several status and diagnostic functionalities.
Used in connection with the corresponding motherboard, two Gateways
Subject to reasonable modifications due to technical advances.
14
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
P R O F I B U S P
O W E R
H
S
U B
E G M E N T
Copyright Pepperl+Fuchs, Printed in Germany
C
O U P L E R

Advertisement