P R O F I B U S P
O W E R
Cyclic data exchange can be connected redundantly to the DP line by
using the redundant Gateway Motherboard MB-FB-GTR and two
HD2-GTR-4PA Gateways.
The
Gateway
"Flying Redundancy" (chapter "Redundancy Concepts" on page 63) as
well as all non-redundant DP Masters.
In summary, the Gateway is responsible for the following tasks:
•
Conversion of the PROFIBUS DP physical layout to that of the
PROFIBUS PA
•
Adjusting the DP transmission rate to the PA transmission rate
•
Galvanic isolation between PROFIBUS DP and PA
•
Elementary functional diagnostics via LEDs
•
Ensuring increased availability through redundant coupling of
cyclic data exchange (with redundant layout)
•
Acyclic Parameterization of Gateway parameters by
FDT/DTM
•
Redundancy diagnostics (with redundant layout)
2.3
Segment Supply
Power is supplied to the field devices through Power Hub Modules on a
Power Hub Motherboard (simplex: 4 Power Hub connection slots, red-
undant: 8 connection slots) and via bus lines to the individual segments.
PA segments can receive redundant power supply if the redundant Po-
wer Hub Motherboard is used along with two Power Hub Modules for
each segment.
In summary, the supply is responsible for the following tasks:
•
Power supply of field devices: power and communication signal
•
Redundant supply for high system availability
•
Elementary diagnostic information via LEDs
•
Advanced Physical Layer Diagnostics via the HD2-DM* Diagno-
stic Module and the FDT/DTM software package (see corre-
sponding documentation).
2.4
System Components
2.4.1
Motherboards
Gateway motherboard simplex MB-FB-GT
The gateway motherboard simplex MB-FB-GT allows the connection of
the Fieldbus Power Hub motherboards MB-FB*.GEN or MBHD-
FB*.GEN using a standard cable. A socket will hold the DP/PA Gateway
HD2-GTR-4PA. The Built-In Slave of the HD2-GTR-4PA can be addres-
sed using the DIP switch on the motherboard.
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
H
S
U B
E G M E N T
Module
HD2-GTR-4PA
C
O U P L E R
supports
Copyright Pepperl+Fuchs, Printed in Germany
Specification
PROFIBUS
13