ID50 Series Panel - Operating Manual

3.4 Plant Alarm

A
PLANT
< - - - Zone Text - - - > < - - - Device Text - - - >
Status: NORMAL
Sat 01/12/2001
3.5 Fault Output: Fault /Disabled (Optional)
A Plant Alarm indication is the default configuration setting
for ID50 Series fire control panels. In this configuration,
the panel operates as follows:
A Plant Alarm message is displayed if the panel detects
a non-fire input (AUX) configured in zones 17 to 32. When
a non-fire event occurs the Plant Alarm LED is illuminated
(except for Hold Switch and Abort Switch AUX inputs)
and the LCD displays the following information:
a. Plant Alarm condition.
b. Alarm number currently displayed.
c. Number of alarms.
d. Zone number.
e. Device address.
f. Device type.
g. Time of logged message.
h. Zonal and device text (if any).
B
C
D
01 / 01
Z21
H
When the cause of the alarm has been cleared, the
message will automatically be removed from the LCD
and the LED extinguished. The panel returns to quiescent
mode.
00:00:00
If the panel has been configured to indicate the status of
the Fault Output relay circuit, a message is displayed if a
Fault Output relay circuit fault condition is detected or if it
has been disabled.
Note: An output device configured to a Fault CBE rule
remains active if disabled from a source other than
the panel Fault Output relay disable function.
11
E
F
M12
MCP
14:55
G
997-264-000-8, Issue 8
January 2007