7
[U0 VOLTS]
[U0 ANALOGUE]
2
[U0 ANALOGUE]
[U0 ANALOGUE]
ID50 Series Panel - Operating Manual

4.12.7 Voltages - User Option

The Voltages User Option allows the user to view the
Voltages of various parts of the system. To view these
Voltages, from the View Mode menu:
1 Using the numeric keypad, press the '
select the Voltages menu.
[U0 View]
8: Voltages
* ID60 Panels only.
2 The Battery Volts window is automatically displayed.
Press the '
system voltage.
BATTERY VOLTS = 27.0
: Select
<:Cancel
EARTH = 271
: Select
[U0 ANALOGUE]
[U0 ANALOGUE]
[U0 VOLTS]
[U0 VOLTS]
Note: The voltage displayed for each system should be
a. Mains supply present: a battery voltage value greater
than 15V means that batteries are connected; battery
voltage is low if greater than 15V but less than 18.9V.
No mains supply present: a value of less than 22V
means an imminent deep discharge; a value less than
21V indicates deep discharge of the batteries.
b. An Earth Fault is indicated when the displayed value
is less than 175 or greater than 450.
c. A Sounder is open circuit if the displayed value is
below 75, or short circuit if above 250.
d. A mains failure is detected when the AC voltage drops
below 193Vac. This fault will remain until the AC
voltage rises above 205Vac.
e. The Charger is faulty if a value less than 24V is
displayed.
3 Press the '
Mode menu.
43
6:
Maint.*
7: Alarm Count
9: Version
/
' buttons to display the previous/next
2
8
8
<:Cancel
SOUNDER 1 = 164
: Select
<:Cancel
SOUNDER 2 = 164
: Select
<:Cancel
SOUNDER 3 = 164
: Select
<:Cancel
SOUNDER 4 = 164
: Select
<:Cancel
AC POWER = 237
: Select
CHARGER = 27.2
: Select
within a given range.
' button to cancel and return to the View
4
' button to
7
: More
<:Cancel
<:Cancel
997-264-000-8, Issue 8
January 2007