ID50 Series Panel - Operating Manual
Appendix 3
ID60 Single Loop Panel Differences
The ID60 Panel differs from the ID50 Panel in that it
TM
supports Very Intelligent Early Warning (VIEW
) and
SMART 4 multi-criteria sensors. This appendix describes
differences to the user operations required by the ID60
Panel.
TM
VIEW
Sensor
Each VIEW
TM
sensor has to be calibrated on first
operation with the panel. If a VIEW
TM
sensor is removed
and cleaned, or replaced with a new one, wait at least
30 secs after removal before replacing it.
Calibration is carried out automatically for each sensor
approximately 60 secs after the sensor is installed on a
panel which is already operating normally.
Following replacement,
VIEW
TM
sensors remain
During this initial period (which is required to allow the
inoperable for 60 seconds
VIEW
TM
sensor to stabilise) the sensor must not be
while calibrating.
exposed to smoke or any other abnormal conditions,
otherwise the panel may report a sensor fault.
SMART 4 Sensor
No user procedures are required with this sensor.
However, a new advisory message is logged whenever
a SMART 4 device approaches the end of the useful life
of the CO sensor element (approximately 6 months before
the sensor needs a complete replacement). A new print
option is available with the ID60 that allows printing of
the maintenance log. It is still possible to print the
maintenance log even if it contains no entries. The print
out will confirm that the maintenance log is empty.
A3 - 1
997-264-000-8, Issue 8
January 2007