27a
Cut-in and cut-out temperatures
at storage tank charging - lines
1-7, circuit II
1
Primary storage tank temperature difference
Circuit
Setting range
II
Set the difference between the cut-in (start) temperature and the
cut-out (stop) temperature for DHW charging.
Set the primary storage tank temperature
difference.
Temp.
Charging
2
Return temperature difference
Circuit
Setting range
II
Set the difference between the return storage tank and heating
return temperatures.
Set the return storage tank and heating return
temperature difference..
Temp.
M3
ON
OFF
3
Max. charging time, M3
Circuit
Setting range
II
5 ... 250 min.
Set the max. time that M3 can be open until the desired primary
tank temperature (S5) is reached.
Set the max. opening time for M3.
The grey
side of the
ECL Card
Factory setting
1 ...30 K
6 K
Primary storage
tank temp.
difference, line 1
Actual DHW temp.
Desired storage
tank temp.
Temp (S5)
Time
Factory setting
1 ...30 K
4 K
Storage tank temp.
(S2)
Return temp. (S4)
Temp. difference
line 2, minus 2
Temp. difference
line 2
Time
Factory setting
40 min.
5
Acceptable temperature deviation below desired
flow temperature
Circuit
Setting range
II
OFF / 1 ... 30 K
M3 is closed if the actual flow temperature drops too much below
the desired flow temperature. The max. deviation is set here.
This condition must last longer than the time intervalset in line 7.
See also line 6.
OFF: M3 is not active.
1 ... 30:
M3 close is active if the actual temperature
falls below the acceptable deviation.
6
Acceptable temperature deviation above the desired
flow temperature
Circuit
Setting range
II
M3 is closed if the actual flow temperature rises too much above
the desired flow temperature. The max. deviation is set here.
This condition must last longer than the set time interval in line 7.
This function can only be activated if the value in line 5 is set to
1 ... 30 K.
1 ... 30: The M3 close function is active if the
actual temperature rises above the
acceptable deviation.
7
Time interval before closing M3
Circuit
Setting range
II
1 ... 99 min.
If a condition from either line 5 or 6 is present for a longer time
than the time interval set here, M3 closes.
1 ... 99: Time interval.
S3 flow temp.
M3
ON
OFF
27b
27b
Factory setting
5 K
Factory setting
1 ... 30 K
5 K
Factory setting
10 min.
S3 flow temp.
Upper deviation
(line 6)
Lower deviation,
(line 5)
Time
Time interval (line 7 )
The grey
side of the
ECL Card