6. Other

6.3. Possible Setting Range for Maximum Scale

The maximum scale of current can be selected from about 40% to 120% of rating, and maximum scale of voltage can be
selected from about 20% to 250% of rating, and maximum scale of active power and reactive power can be selected from
about 20% to 120% of rating. But for the convenience of scale conditions, the values in the following tables are applied.
Also, this is same as with corresponding measured values for maximum scale of analog output.
■Current maximum scale value
Possible setting range:-10 STEP to +3STEP of the rating
Example: When the rating is 100A, the value is from 45A to 160A.
Current maximum scale value (1/3)
STEP
A unit
1
1A
2
1.2A
3
1.5A
4
1.6A
5
1.8A
6
2A
7
2.2A
8
2.4A
9
2.5A
10
3A
11
3.2A
12
3.6A
13
4A
14
4.5A
15
4.8A
16
5A
17
6A
18
6.4A
19
7.2A
20
7.5A
21
8A
22
9A
23
9.6A
24
10A
25
12A
26
15A
27
16A
28
18A
29
20A
30
22A
31
24A
32
25A
33
30A
34
32A
35
36A
36
40A
37
45A
38
48A
39
50A
40
60A
41
64A
42
72A
43
75A
44
80A
45
90A
46
96A
47
100A
48
120A
49
150A
50
160A
Current maximum scale value (2/3)
STEP
A unit
kA unit
51
180A
52
200A
53
220A
54
240A
55
250A
56
300A
57
320A
58
360A
59
400A
60
450A
61
480A
62
500A
63
600A
64
640A
65
720A
66
750A
67
800A
68
900A
69
960A
70
1000A
71
1200A
72
1500A
73
1600A
74
1800A
75
2000A
76
2200A
77
2400A
78
2500A
79
3000A
80
3200A
81
3600A
82
4000A
83
4500A
84
4800A
85
5000A
86
6000A
87
6400A
88
7200A
89
7500A
90
8000A
91
9kA
92
9.6kA
93
10kA
94
12kA
95
15kA
96
16kA
97
18kA
98
20kA
99
22kA
100
24kA
80
Current maximum scale value (3/3)
STEP
kA unit
101
25kA
102
30kA
103
32kA
104
36kA
105
40kA