Setting Menu 6: Setting The Logging Function - Mitsubishi Electric ME96SSRA-MB User Manual

Electronic multi-measuring instrument
Hide thumbs Also See for ME96SSRA-MB:
Table of Contents

Advertisement

3. Setting
3.10.

Setting Menu 6: Setting the Logging function

This section shows how to set the logging function. When the ME-0000BU-SS96 optional plug-in module is not installed, this menu will be skipped.
In the operation mode, press
SET
Setting Menu
DISPLAY
SET
①Logging ID
DISPLAY
SET
②Logging Data Clear
DISPLAY
SET
③Logging-item
pattern
DISPLAY
SET
and
simultaneously for 2 seconds or more, and the following operation becomes available.
RESET
Set the setting menu number to "6".
(as shown in the right figure)
Set the ID number of the optional plug-in module: ME-0000BU-SS96.
Settable ID : 001 to 255
When ID number installed of the optional plug-in module is set,
that ID number is appeared as the initial value.
If ME96SS cannot receive the setting value of logging ID from
Note
ME-0000BU-SS96, the screen does not appear. Just wait there for a moment.
Clears logging data memorized in optional plug-in module:
ME-0000BU-SS96.
no
(Not clear)
When "yES(Clear)" is selected at the above setting, the confirmation screen appears
in order to reconfirm whether the logging data can be cleared or not.
no
(Not clear)
Set the Logging-item pattern to select the logging items.
Settable pattern :
When LP00 is set, you can choose any 6-item.
(For details of LP00, refer to following manual:
ME-0000BU-SS96:Logging specifications ............ LSPM-0092)
The logging-item pattern of LP01 and LP02 is defined as follows.
"Detailed data" is memorized shorter cycle than "One-hour data".
Logging cycle of "Detailed data" is set in ④Detailed data logging cycle .
Phase-wire setting: 3P4W
Logging-item
pattern
Detailed data
Data 1
Data 2
varh(import LAG)
Data 3
Data 4
Data 5
Data 6
Phase-wire setting: 3P3W_2CT, 3P3W_3CT, 1P3W
Logging-item
pattern
Detailed data
Data 1
Wh(import)
varh(import LAG)
Data 2
Data 3
Data 4
Data 5
Data 6
yES
(Clear)
yES
(Clear)
LP01
LP02
LP01
One-hour data
Wh(import)
Wh(import)
Wh(export)
VAh
varh(import LAG)
DW
varh(import LEAD)
Dvar
VAh
DVA
-
LP01
One-hour data
Wh(import)
Wh(export)
VAh
varh(import LAG)
DW
varh(import LEAD)
Dvar
VAh
DVA
-
42
LP00
LP02
Detailed data
One-hour data
Wh(import)
Wh(import)
A
Wh(export)
AVG
V
(L-L)
varh(import LAG)
AVG
W
varh(import LEAD)
Σ
PF
VAh
Hz
-
LP02
Detailed data
One-hour data
Wh(import)
Wh(import)
A
Wh(export)
AVG
V
varh(import LAG)
AVG
W
varh(import LEAD)
PF
VAh
Hz
-

Advertisement