Applicable Standards; Specifications Of Modbus Rtu Communication; Specifications Of Cc-Link Communication - Mitsubishi Electric ME96SSRA-MB User Manual

Electronic multi-measuring instrument
Hide thumbs Also See for ME96SSRA-MB:
Table of Contents

Advertisement

Specifications

2. Applicable Standards

Electromagnetic Compatibility
Emissions
Radiated Emission
Conducted Emission
Harmonics Measurement
Flicker Meter Measurement
Immunity
Electrostatic discharge Immunity
Radio Frequency Electromagnetic field Immunity
Electrical Fast Transient/Burst Immunity
Surge Immunity
Conducted Disturbances, Induced By Radio Frequency Fields Immunity
Power Frequency Magnetic Field Immunity
Voltage Dips and Short Interruptions
Safety
Europe
U.S. and Canada
Installation Category
Measuring Category
Pollution Degree
3. Specifications of MODBUS
Item
Physical interface
Protocol
Synchronization method
Network topology
Baud rate
Data bit
Stop bit
Parity
Slave address
Distance
Maximum Number
Response time
Terminate
Recommended cable
 About Programming
In addition to this manual, read the following documents too.
 Electronic Multi-Measuring Instrument ME Series MODBUS® Interface specifications ..................................... LSPM-0075

4. Specifications of CC-Link Communication

Item
CC-Link station type
Number of occupied stations
CC-Link version
Transmission speed
Maximum number of connected
stations
 CC-Link Dedicated Cable
Use the CC-Link dedicated cables for the CC-Link system. If a cable other than the CC-Link dedicated cable is used, the
performance of the CC-Link system cannot be guaranteed.
For the specifications of the CC-Link dedicated cables or any other inquiries, visit the following website:
CC-Link Partner
Association:http://www.CC-link.org/
REMARK
For details, refer to the CC-Link cable wiring manual issued by CC-Link Partner Association.
 About Programming
In addition to this manual, read the following documents too.
 Electronic Multi-Measuring Instrument programming manual (CC-Link) ............................................................ LEN080334
 Electronic Multi-Measuring Instrument programming manual (CC-Link)(For ver. 2 remote device station)......... LEN130391
Note1: As for details, refer to the above manuals.
CE, as per EN61010-1
cRUus as per UL61010-1, IEC61010-1
2
®
RTU Communication
RS-485 2wires half duplex
RTU (Binary data)
Start-stop synchronization
Daisy-chain
2400, 4800, 9600, 19200, 38400bps
8
1, 2
Odd, Even, None
1 to 255 (0:For broadcast)
1200m
31
1s or less (time to a response after receiving a query)
120Ω 1/2W
Shielded twisted pair, AWG24 to 14 gauge
Remote device station (ver.1 remote device station or ver.2 remote device station)
Ver.1 remote device station (ver.1 compatible slave station) setting: 1 station
Ver.2 remote device station (ver.2 compatible slave station) setting: 1 station (Expanded
cyclic setting: Octuple)
CC-Link Ver 1.10 / 2.00
Can select from 156kbps / 625kbps / 2.5Mbps / 5Mbps / 10Mbps
If the system is configured by only this instrument, up to 42 units can be connected.
(note1)
102
EN61326-1/CISPR 11,
FCC Part15 Subpart B Class A
EN61326-1/CISPR 11
FCC Part15 Subpart B Class A
EN61000-3-2
EN61000-3-3
EN61326-1/EN61000-4-2
EN61326-1/EN61000-4-3
EN61326-1/EN61000-4-4
EN61326-1/EN61000-4-5
EN61326-1/EN61000-4-6
EN61326-1/EN61000-4-8
EN61326-1/EN61000-4-11
Specifications
Specifications

Advertisement

Table of Contents
loading