Cooling With 3-Stage Reheat And Night Setback/Setup - KMC Controls CTE-5202 Application Manual

Analog electronic thermostat w/ lcd display
Hide thumbs Also See for CTE-5202:
Table of Contents

Advertisement

Cooling with 3-Stage Reheat and Night Setback/Setup

This configuration is the same as on the previous
page except for the addition of an SPST relay or
switch.
See
Cooling and 3-Stage Reheat on page
35.
The switch or relay is driven by a night/unoccupied
setback/setup signal from other equipment not
shown. When the contact is closed (e.g., by a timer),
setback/setup mode initiates, changing the setpoint
by the offset selected in ADVANCE > SETBACK
menu. See
Change Configuration on page 6
Unoccupied/Standby Setback on page
NOTE: The night/unoccupied setback offset does
not apply to morning warm-up.
CSP-5001
Controller-Actuator
(To Flow Sensor)
H
16
V
I
DC
N
24 VAC Contactors
(10 VA Max. per Stage)
Pressure Independent VAV Applications with CSP-5001/5002
and
5.
L
O
U
24 VAC
~
T
1
2
3
NOTE: This configuration requires the system fan
to be on during setback/setup mode.
NOTE: Triac outputs on the REE-5001 are for 24
VAC loads only. The phase side of the
transformer connects to the "common" side
of the load (contactors).
NOTE: See also the
(See also the Cooling with 3-Stage Reheat and Night
Setback/Setup section with a CTE-5104 in the
5001/5002 Applications
~
(Phase)
24 VAC @ 34 VA
(Neutral)
Select Sequence 2,
with or without
Auxiliary Flow
REE-5001 Relay Module
36
REE-5001 Installation
Guide.)
CTE-5202
Thermostat
SPST
Relay
CTE-5202 Applications Guide, AN0912A Rev. D
Guide.
CSP-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents