Dual Duct Heating And Cooling Vav - KMC Controls CTE-5202 Application Manual

Analog electronic thermostat w/ lcd display
Hide thumbs Also See for CTE-5202:
Table of Contents

Advertisement

Dual Duct Heating and Cooling VAV

Dual duct applications connect two CEP-4000 series
controllers, mounted separately on the hot and cold
air-duct dampers, with each controller using its own
flow sensor.
The hot deck controller receives its requested flow
signal from AO2 on the CTE-5202, while the cold
deck uses the AO1 signal. Both controllers can be
set independently for minimum and maximum flow
settings.
Sequence 3 should be selected from the CTE-5202
SYSTEM menu. See
Change Configuration on page
(See also the (Dual Duct) Heating and Cooling VAV
section with a CTE-1103 in the
Applications
Guide.)
Minimum Air from Cooling
Minimum Air from Cooling
3000
3000
fpm
fpm
Heating Max.
Heating Max.
Min.–3000 fpm
Min.–3000 fpm
Air
Air
Flow
Flow
0 fpm
0 fpm
Heating Setpoint
Heating Setpoint
(Colder
(Colder
Room Temperature
Room Temperature
Minimum Air from Heating
3000
fpm
Heating Max.
Min.–3000 fpm
Air
Flow
0 fpm
Heating Setpoint
(Colder
Room Temperature
Pressure Independent VAV Applications with CEP/CSP-4000 Series
CEP-4000 Series
24 VAC @ 20 VA
(Neutral)
(Phase)
~
Cooling Max.
Cooling Max.
Min.–3000 fpm
Min.–3000 fpm
Cooling
Cooling
Min.
Min.
0–3000
0–3000
fpm
fpm
Cooling Setpoint
Cooling Setpoint
Warmer)
Warmer)
Cooling Max.
Min.–3000 fpm
Cooling
Min.
0–3000
fpm
Cooling Setpoint
Warmer)
6.
Select Sequence 3
CEP-4xxx
Controller-Actuator
8
9
10
11
12
13
14
(Hot Deck)
SSE-1001/1002
Flow Sensor
CEP-4xxx
Controller-Actuator
8
9
10
11
12
13
14
(Cold Deck)
SSE-1001/1002
Flow Sensor
52
7
6
5
4
3
2
1
1
2
3
7
6
5
4
3
2
1
1
2
3
CTE-5202 Applications Guide, AN0912A Rev. D