Chilled Beam Cooling
This application controls cooling in a chilled beam or
equivalent installation.
This works for NC 2–10 and 0–10 VDC valves or NO
10–2 and 10–0 VDC valves.
Single-Zone Heating and Cooling Applications
Valve
24 VAC
(Neutral)
–
(Phase)
~
Cooling Min.
Setpoint
(Colder
Select Sequence 1 (from the CTE-5202 SYSTEM
menu). See
Change Configuration on page
CTE-5202
Thermostat
Cooling Max.
Room Temperature
Warmer)
13
6.
Select Sequence 1
CTE-5202 Applications Guide, AN0912A Rev. D