Cooling and 3-Stage Reheat

This application uses a CSP-5001 along with an
REE-5001 relay module and three 24 VAC contactors
for three stages of reheat.
As the temperature drops below setpoint, the first
stage of reheat begins. As the temperature continues
to drop, the second stage and later the third stage
begin as needed.
CSP-5001
Controller-Actuator
(To Flow Sensor)
H
L
16
O
I
V
U
24 VAC
~
DC
N
T
24 VAC Contactors
1
2
3
(10 VA Max. per Stage)
Pressure Independent VAV Applications with CSP-5001/5002
~
(Phase)
24 VAC @ 34 VA
(Neutral)
Select Sequence 2,
with or without
Auxiliary Flow
REE-5001 Relay Module
9.5 V
6.5 V
Reheat
3.5 V
Stages
#3
#2
12 Volts
#1
AUX
10%
Of Loop
2° F
Heating
Setpoint
Select Sequence 2 (from the CTE-5202 SYSTEM
menu), with or without Auxiliary Flow (AO1 AUX
in LIMITS menu). See
page
6.
(See also the Cooling with 3-Stage Reheat section
with a CTE-5104 for auxiliary flow or a CTE-5103
without auxiliary flow in the
cations
Guide.)
CTE-5202
Thermostat
COLD AIR SEQUENCE
AO2 (RA)
AO1 (DA)
2° F
Cooling
Temp. Increasing
Setpoint
35
Change Configuration on
CSP-5001/5002 Appli-
NOTE: Triac outputs on
the REE-5001
are for 24 VAC
loads only. The
phase side of
the transformer
connects to
the "common"
side of the load
(contactors).
NOTE: See also the
5001 Installation
Guide.
0 Volts
AO1 MAX
AO1 MIN
CTE-5202 Applications Guide, AN0912A Rev. D