Cooling
CTE-5202 thermostats can use CEP/CSP-4000 series
electronic VAV controllers to operate damper boxes
in a pressure-independent VAV system. As shown
in the diagram, a "requested flow" voltage signal
(AO1) is connected to the CEP-4xxx to adjust airflow
from minimum to maximum flow according to
space demand. Minimum and maximum flow limit
adjustments can be made at the thermostat or at the
controller.
24 VAC @ 10 VA
(Neutral)
(Phase)
Pressure Independent VAV Applications with CEP/CSP-4000 Series
CEP-4xxx
Controller-Actuator
8
9
–
~
10
11
12
13
14
SSE-1001/1002
Flow Sensor
3000
fpm
Air
Flow
Cooling Min.
03000 fpm
0 fpm
Setpoint
(Colder
Select Sequence 1 (from the CTE-5202 SYSTEM
menu). See
Change Configuration on page
replaces a CTE-1001/1101/5001/5011 with Direct
Acting reset.)
(See also the Cooling section in the
Applications
Guide.)
Select Sequence 1
7
6
5
4
3
2
1
1
2
3
Cooling Max.
Min.3000 fpm
Room Temperature
Warmer)
45
6. (This
CEP-4000 Series
CTE-5202
Thermostat
CTE-5202 Applications Guide, AN0912A Rev. D