Cooling with Heating Changeover

Using a duct sensor with the CTE-5202, an automatic
changeover is provided for cooling/heating applica-
tions. The duct sensor will switch the thermostat
between cooling and heating modes based on the
temperature of the duct supply air. A duct tempera-
ture higher than changeover temperature switches
control to heating mode, and a temperature lower
than changeover temperature switches control to
cooling mode.
COLD AIR SEQUENCE
AO1 MIN
2° F
Pressure Independent VAV Applications with CSP-4702
CSP-4702
Controller-Actuator
(To Flow Sensor)
24 VAC @ 5 VA
(Phase)
~
(Neutral)
STE-140x Duct Temp. Sensor
AO1 (DA)
2° F
Setpoint
Select Sequence 1 (from the CTE-5202 SYSTEM
menu). See
Change Configuration on page 6
Hot/Cold Changeover on page
changeover temperature is 77° F, configurable from
55 to 85° F in the CTE-5202 ADVANCE menu.
NOTE: Minimums can be set at zero air flow, but a
minimum of greater than zero is required
for a quick changeover.
Select Sequence 1
AO1 MAX
AO1 MAX
Temp. Increasing
26
5. The default
CTE-5202
Thermostat
HOT AIR SEQUENCE
AO1 (RA)
2° F
Setpoint
CTE-5202 Applications Guide, AN0912A Rev. D