Cooling with Heating Changeover

Using a duct sensor with the CTE-5202, an automatic
changeover is provided for heating/cooling applica-
tions. The duct sensor will switch the thermostat
between cooling and heating modes based on the
temperature of the duct supply air. A duct tempera-
ture higher than changeover temperature switches
control to heating mode, and a temperature lower
than changeover temperature switches control to
cooling mode.
Select Sequence 1 (from the CTE-5202 SYSTEM
menu). See
Change Configuration on page 6
Cold Changeover on page
temperature is 77° F, configurable from 55 to 85° F in
the CTE-5202 ADVANCE menu.
Controller-Actuator
(To Flow Sensor)
H
16
I
V
N
DC
COLD AIR SEQUENCE
AO1 MIN
2° F
Pressure Independent VAV Applications with CSP-5001/5002
and
5. The default changeover
CSP-5001
L
O
U
24 VAC
~
T
TTE-2001 or STE-140x Duct Sensor
AO1 (DA)
2° F
Setpoint
NOTE: The CTE-5202 uses the 16 VDC power
from the CSP-5001. If replacing a CTE-5103
thermostat as described in the Cooling and
Heating Changeover section of the
5001/5002 Applications
1005 relay module is no longer needed with
the CTE-5202.
NOTE: If using an existing TTE-2001 duct sensor/
transmitter (instead of an STE-140x duct
sensor), connect to Terminals 1 and 2.
Hot/
NOTE: Minimums can be set at zero air flow, but a
minimum of greater than zero is required
for a quick changeover.
~
(Phase)
24 VAC @ 4 VA
(Neutral)
Select Sequence 1
1
2
3
AO1 MAX
AO1 MAX
Temp. Increasing
37
Guide, the REE-
CTE-5202
Thermostat
HOT AIR SEQUENCE
AO1 (RA)
2° F
Setpoint
CTE-5202 Applications Guide, AN0912A Rev. D
CSP-
AO1 MIN