Replacing A Cep-4Xxx Or Csp-40Xx/42Xx/44Xx/46Xx - KMC Controls CTE-5202 Application Manual

Analog electronic thermostat w/ lcd display
Hide thumbs Also See for CTE-5202:
Table of Contents

Advertisement

Replacing a CEP-4xxx or CSP-40xx/42xx/44xx/46xx

With changes to the sensors, the CSP-4702 can
generally be used in any of the older CEP-4xxx and
CSP-40xx/42xx/44xx/46xx applications shown in the
section
Pressure Independent VAV and CAV Applica-
tions with CEP/CSP-4000 Series on page
Although it may sound as if it belongs in the same
series, the new CSP-4702 is quite different from the
old CSP-40xx/42xx/44xx/46xx models. There are
some differences among the models of which the
installer must be aware:
• CEP-4xxx and CSP-40xx/42xx/44xx/46xx control-
lers supply 9.1 VDC for connected thermostats.
The CSP-4702 (like the CSP-500x controllers)
outputs 16 VDC. When replacing an older
controller, any connected thermostat that oper-
ates from 9.1 VDC power must also be:
• Replaced with the
from the 16 VDC supplied by the CSP-4702.
• Or powered by an
(connected to the transformer) to deliver 9.1
VDC to the existing thermostat.
• If replacing a CEP-4xxx, an attached SSE-xxxx
sensor must be replaced with an SSS-
1xxx sensor. For an existing SSE-200x
used for duct temperature sensing,
terminals X and Y can continue to be
used for duct temperature sensing,
and an SSS-1xxx air flow sensor can be
installed separately.
• If a CSP-4702 is used to replace an
existing CxP-4xxx and limits were set in
the CxP-4xxx, the limits will need to be
set (in either the CSP-4702 or the thermo-
stat). If a CSP-4702 is used to replace an
existing CxP-4xxx and limits were set in
the thermostat, the limits in the thermo-
stat should be checked and adjusted to
ensure accuracy.
Pressure Independent VAV Applications with CSP-4702
43.
CTE-5202
that operates
XEE-4002
power supply
Controller-Actuator
24 VAC @ 5 VA
• The terminals on a CxP-4xxx are very different
than on a CSP-4702:
• 10 = 24 VAC phase
• 9 = 24 VAC neutral/common
• 6 = Input from thermostat
• 5 = Power (VDC) to thermostat
• 4 = Common
• 3, 2, and 1 = to SSE-1xxx flow sensor, no
longer used (but SSE-2xxx sensors can still be
used for duct temperature sensing)
NOTE: Compare the wiring of the CSP-4702
version of cooling with heating changeover
below to the CEP-4xxx version in
Heating Changeover on page
Cooling with Heating Changeover on page
26.
CSP-4702
(To Flow Sensor)
~
(Phase)
(Neutral)
1
SSE-2001/2002
2
3
Y
X
21
Cooling/
48. See also
CTE-5202
Thermostat
(Flow Sensor
Disconnected)
Temperature Sensor
CTE-5202 Applications Guide, AN0912A Rev. D