Setback (OAT) Lockout Setup

SETBACK LOCKOUT
OAT LOCKOUT:
LOCKOUT TEMP: 30° F
Setback OAT lockout is disabled by default. When
enabled, AI4 is configured for OAT and the Lockout
Temp selection appears in the menu. This may be
useful when a system, such as an HPU, may have
difficulty recovering from the unoccupied setpoint to
the occupied setpoint during very cold weather.
NOTE: When enabled, the default value is 30° F
(–1° C) for HPU and 10° F (–12° C) for all
other applications. The value is adjustable
between –50 and 120° F (–45.5 and 49° C).

Staging Setup

STG DELAY (MINS):
After the first stage starts in multistage heating or
cooling, the default delay time before the second
stage can start is 3 minutes.

Valve Setup

VALVE SETUP
CLG (0–100%):
HTG (0–100%): 0–10V
Proportional valves have a 0–10 VDC default for
0–100% open. Change as needed (e.g., 10–2 VDC).
FlexStat
ENABLE
STAGING
3
0–10V

(Advanced) CB (Control Basic) Programs

CB PROGRAMS
PROG1:
RUNNING
PROG2: RUNNING
PROG3: RUNNING
PROG4: RUNNING
PROG5: RUNNING
PROG6: HALTED
PROG7: IDLE
To halt or load/run the built-in (1–5) and custom
(6–10) Control Basic programs, navigate to the de-
sired line and selection.
If custom Control Basic programs are installed and a
restore to factory settings is performed, all factory
programs are restarted but all custom Control Basic
programs are halted. Change the state of each pro-
gram by loading/running the program from the CB
Programs menu (or BACstage or TotalControl).
If custom Control Basic programs are installed and
set to autorun, whenever the firmware is updated,
ALL (factory and custom) programs are halted. If
custom Control Basic programs are installed but
NOT set to autorun, whenever the firmware is up-
dated, factory programs are restarted but any (manu-
al) running custom programs are halted at restart.
Change the state of each custom program by using
the Update Manager or loading/running each pro-
gram from the CB Programs menu (or BACstage or
TotalControl).
UPDATE MANAGER
PROGRAM CONFIG ERROR
ENABLE FACTORY:
ENABLE CUSTOM: NO
EDIT CB PROGRAMS
DONE
In the About menu, ASV will show CUSTOM if any
built-in Control Basic program (1–5) is not running
or has auto-run disabled. See About the FlexStat on
page
6.
NOTE: Customized programs are the responsibility
of the user. KMC Controls does not provide
support for such programs.
10
PROGRAM #1
SETPOINTS & MODES
AUTO-RUN: TRUE
CHANGE: READY
STATE: RUNNING
HALT REASON: NORMAL
HALT DESC:
OUT OF SERVICE: FALSE
NO