Dual Duct, Minimum Air From Cold Duct - KMC Controls CTE-5202 Application Manual

Analog electronic thermostat w/ lcd display
Hide thumbs Also See for CTE-5202:
Table of Contents

Advertisement

Dual Duct, Minimum Air from Cold Duct

Dual duct applications can use two CSP-4702s with
a CTE-5202. In this application, the CSP-4702s are
mounted separately on the cold and hot air duct
dampers with each using its own flow sensor.
The cold-deck controller receives the AO1 signal
from the thermostat while the hot-deck controller
Cold Deck
CSP-4702
Controller-Actuator
24 VAC @ 10 VA
~
(Phase)
(Neutral)
Pressure Independent VAV Applications with CSP-4702
(To Flow Sensor)
AO2 MAX
AO1 MIN
2° F
Heating
Setpoint
receives its requested flow signal from AO2. Both
CSP-4702s can be set independently for minimum
and maximum flow settings.
Select Sequence 3 (from the CTE-5202 SYSTEM
menu). See
Change Configuration on page
Hot Deck
CSP-4702
(To Flow Sensor)
Controller-Actuator
AO2 (RA)
AO1 (DA)
2° F
Cooling
Temp.
Setpoint
Increasing
31
6.
Select
Sequence
3
CTE-5202
Thermostat
AO2 MIN
AO1 MAX
CTE-5202 Applications Guide, AN0912A Rev. D