Cooling with Heating Changeover and Electric Reheat

This configuration is the same as the previous page
except for the addition of an REE-5001 relay module
connected to AO2 (for three stages of reheat) and
selecting Sequence 2 from the CTE-5202 SYSTEM
menu. See
Change Configuration on page
Cold Changeover on page 5
Heating Changeover on page
and 3-Stage Reheat on page
CSP-4702
Controller-Actuator
24 VAC @ 35 VA
~
(Phase)
(Neutral)
24 VAC Contactors
1
2
3
(10 VA Max. per Stage)
9.5 V
6.5 V
Reheat
3.5 V
Stages
#3
#2
12 Volts
#1
AUX
10%
Of Loop
2° F
Heating
Setpoint
Pressure Independent VAV Applications with CSP-4702
6,
Hot/
and
Cooling with
26. See also
Cooling
24.
(To Flow Sensor)
REE-5001 Relay Module
COLD AIR SEQUENCE
AO2 (RA)
AO1 (DA)
2° F
Cooling
Setpoint
NOTE: Minimums can be set at zero air flow, but a
minimum of greater than zero is required
for a quick changeover.
NOTE: Triac outputs on the REE-5001 are for 24
VAC loads only. The phase side of the
transformer connects to the "common" side
of the load (contactors).
NOTE: See also the
CTE-5202
Thermostat
HOT AIR SEQUENCE (Morning Warm Up)
0 Volts
AO1 MAX
AO1 MAX
AO1 MIN
Temp. Increasing
27
REE-5001 Installation
Select Sequence 2
STE-140x
Duct
Temp.
Sensor
AO1 (RA)
2° F
Heating
Setpoint
CTE-5202 Applications Guide, AN0912A Rev. D
Guide.
AO2 Disabled
(0 Volts)
AO1 MIN