Chilled Beam 2-Pipe Heating And Cooling With Changeover - KMC Controls CTE-5202 Application Manual

Analog electronic thermostat w/ lcd display
Hide thumbs Also See for CTE-5202:
Table of Contents

Advertisement

Chilled Beam 2-Pipe Heating and Cooling with Changeover

An STE-1454/1455 strap-on (Type III) temperature
sensor provides the CTE-5202 an automatic change-
over for heating/cooling applications using hot and
chilled water. The sensor will switch the thermostat
between cooling and heating modes based on
the temperature of the water in the pipe. A water
temperature higher than changeover temperature,
switches control to heating mode, and a temperature
lower than changeover temperature, switches con-
trol to cooling mode.
COLD SEQUENCE
AO1 MIN
2° F
Setpoint
Single-Zone Heating and Cooling Applications
24 VAC
(Neutral)
(Phase)
~
STE-1454/1455 Strap-On Sensor on Supply Pipe
AO1 (DA)
2° F
Select Sequence 1 from the CTE-5202 SYSTEM
menu. Change the default changeover temperature
to the maximum of 85° in the CTE-5202 ADVANCE
menu. See
Change Configuration on page 6
Cold Changeover on page
CTE-5202
Thermostat
Valve
AO1 MAX
AO1 MAX
Temp. Increasing
15
5.
Select Sequence 1
HOT SEQUENCE
AO1 (RA)
2° F
Setpoint
CTE-5202 Applications Guide, AN0912A Rev. D