Cooling and 3-Stage Reheat

This application uses a CSP-4702 along with an
REE-5001 relay module and three 24 VAC contactors
for three stages of reheat.
As the temperature drops below setpoint, the first
stage of reheat begins. As the temperature continues
to drop, the second stage and later the third stage
begin as needed.
CSP-4702
Controller-Actuator
24 VAC @ 35 VA
(Phase)
~
(Neutral)
24 VAC Contactors
1
2
3
(10 VA Max. per Stage)
Pressure Independent VAV Applications with CSP-4702
(To Flow Sensor)
REE-5001 Relay Module
9.5 V
6.5 V
Reheat
3.5 V
Stages
#3
#2
12 Volts
#1
AUX
10%
Of Loop
2° F
Heating
Setpoint
Select Sequence 2 (from the CTE-5202 SYSTEM
menu), with or without Auxiliary Flow (AO1 AUX
in LIMITS menu). See
page
6.
NOTE: Triac outputs on the REE-5001 are for 24
VAC loads only. The phase side of the
transformer connects to the "common" side
of the load (contactors).
CTE-5202
Thermostat
COLD AIR SEQUENCE
AO2 (RA)
AO1 (DA)
2° F
Cooling
Temp. Increasing
Setpoint
24
Change Configuration on
NOTE: See also the
5001 Installation
Guide.
Select Sequence 2,
with or without
Auxiliary Flow
0 Volts
AO1 MAX
AO1 MIN
CTE-5202 Applications Guide, AN0912A Rev. D