7-6 Network Setting

Touch the [Network] tab in the screen that appears when [Initial Settings] on the menu bar in the setting change screen is touched to
open the network setting screen and make the basic settings for LAN and M-NET.
Note: If the user logs in as a building manager, some of the operations may be prohibited.
Note: When changes are made to the settings, restart the AG-150A before going back to the main menu to reflect the those changes.
IP address input
button
Subnet mask
input button
Gateway address
input button
7-6-1
LAN setting
In Network Setting, set the AG-150A IP address, subnet mask and gateway address. If connecting to the AG-150A via a permanent
LAN, consult with the network administrator before setting these addresses.
7-6-1-1 Settings for when the AG-150A is connected to a dedicated LAN
(1) Set the IP address for AG-150A. Enter the IP address on the keyboard that appears when the IP address input button is touched.
If the LAN wiring has been newly set up, allocate IP addresses to the AG-150A units in a sequential order starting with
[192.168.1.1]. For example the first AG-150A unit will receive an IP address of [192.168.1.1], the second AG-150A unit will
receive an IP address of [192.168.1.2] and so on.
The Web Monitor PC that monitors and sets AG-150A will also require network addresses consistent with the rest of the LAN.
Note: When using a AG-150A dedicated LAN, it is recommended to set the IP address as follows.
AG-150A: Between [192.168.1.1] and [192.168.1.40] Web Monitor PC: Between [192.168.1.101] and [192.168.1.150]
IP Address button
(2) Set the subnet mask. Enter the subnet mask address for the AG-150A on the keyboard that appears when the subnet mask input
button is touched. Normally, you should enter [255.255.255.0].
Subnet Mask button
(3) When monitoring remotely or sending error mail via a dial-up router, enter the router IP address in the [Gateway] field. Leave the
gateway address blank when not connecting via a dial-up router.
Note: It is recommended to set the dial-up router IP address to [192.168.1.254]. Refer to the dial-up router instruction manual for
details of how to set the IP address.
Note: It is necessary to connect a modem (analog type or ISDN type) between the dial-up router and telephone line when using
a dial-up router that does not have a built-in modem.
Gateway Address button
(4) Press [Save setting] on the network screen to save the setting.
7-6-1-2 Settings for when the AG-150A is connected to an existing LAN
When connecting the AG-150A to an existing LAN, consult with the network administrator who is responsible for the LAN before
setting the IP address, subnet mask, or gateway address.
– 60 –
M-NET address
input button
K converter
address input
button
Controller setting
(prohibition of local
control)
External input
setting button
Save Settings